6,3 kV Plug - Socket Enclosure
Temperature Rise and Short Circuit Current Withstand Test Report
Dielectric Tests Report
Test Video
4000 Ampere Distribution Board
Short Circuit Current Withstand Test Report
Test Videos
Experiment - 1 : Left Enclosures
Ipeak (Peak Withstand Current): 105 kA
Ith (Short-Time Withstand Current): 50 kA - 1 second
Distance Between Insulators : ~40 cm.
Experiment - 2 : Right Enclosures
Ipeak (Peak Withstand Current): 105 kA
Ith (Short-Time Withstand Current): 50 kA - 1 second
Distance Between Insulators : ~40 cm.
Experiment - 3 : Right Enclosures
Ipeak (Peak Withstand Current): 105 kA
Ith (Short-Time Withstand Current): 50 kA - 1 second
Distance Between Insulators : ~80 cm.
Insulators are connected by 4 points.
Insulators are galvanized from the top.
Experiment - 4 : Phase - Neutral
Ipeak (Peak Withstand Current): 66 kA
Ith (Short-Time Withstand Current): 30 kA - 1 second
Distance Between Insulators : ~80 cm.