6,3 kV Plug - Socket Enclosure

Temperature Rise and Short Circuit Current Withstand Test Report

Temperature Rise and Short Circuit Current Withstand Test Report

 

Dielectric Tests Report

Dielectric Tests Report
 
Test Video
 

4000 Ampere Distribution Board

Short Circuit Current Withstand Test Report

Short Circuit Current Withstand Test Report

 

Test Videos

Experiment - 1 : Left Enclosures
Ipeak (Peak Withstand Current): 105 kA
Ith (Short-Time Withstand Current): 50 kA - 1 second
Distance Between Insulators : ~40 cm.

 

Experiment - 2 : Right Enclosures

Ipeak (Peak Withstand Current): 105 kA

Ith (Short-Time Withstand Current): 50 kA - 1 second
Distance Between Insulators : ~40 cm.
 
Experiment - 3 : Right Enclosures
Ipeak (Peak Withstand Current): 105 kA
Ith (Short-Time Withstand Current): 50 kA - 1 second
Distance Between Insulators : ~80 cm.
Insulators are connected by 4 points.
Insulators are galvanized from the top.
 
Experiment - 4 : Phase - Neutral
Ipeak (Peak Withstand Current): 66 kA
Ith (Short-Time Withstand Current): 30 kA - 1 second
Distance Between Insulators : ~80 cm.